Addressable intelligent fixed temperature heat detector

Addressable intelligent fixed temperature heat detector

可寻址智能固定温度热探测器

3 USD

加入意向
I.产品概述

TP-TD7192可寻址热探测器(以下探测器)是90系列火灾报警控制面板的配套产品。它使用双总线工作模式。使用内部微处理器,它支持电子编码。检测器实现实时获取原位温度数据,并将数据发送回火灾报警控制面板。它还可以接收和执行火灾报警控制面板给出的控制命令。在路由检查中,检测器指示灯将闪烁。当被监控区域有火灾并且温度已经达到报警阈值时,火灾报警控制面板将根据从检测器发送的接收信息确认火灾报警,同时检测器指示灯将亮起,火灾报警

该检测器适用于在发生火灾时具有大量热量的工业和民用建筑物,例如厨房,锅炉室,发电机室,干燥车间和吸烟室,并且不适合于具有大量烟雾的地方,少热

II。产品特点

它可以实现电子编码和通过编码器原地重写地址

在单片微机中,可以实现实时数据采集和处理,实现对现场情况的曲线跟踪

它具有温度补偿功能和传感器故障检测功能(故障报告给火灾报警控制面板)

非极性,双总线连接,确保安装和维护方便

设计有上盖和下盖,并安装在独立基座上,可以方便地安装,调试和维护

III。技术参数

执行标准:GB4716-2005
工作电压:24V(脉冲调制)
工作电流: <300uA (monitoring status) or <1.5mA (alarm status)
工作指示:红色指示灯在监视状态下闪烁,或在报警状态下保持点亮
重量:约47g
产品类别:A2
外形尺寸:直径:100mm,高度:56mm(带底座)
接线方式:非极性双母线系统(L1,L2)
操作环境:室内,温度: - 10°C + 50°C,相对湿度:≤95%(40°C±2°C,无冷凝)
编码模式:可以通过编码器原位实现电子编码。地址代码1至324可供选择。
安装高度:≤8m

防护面积:约60m2。详见“GB50116-98自动火灾报警系统设计规范”相关规定
匹配主机:火灾报警控制面板(如TP-AL7130)

I. Product overview

TP-TD7192 addressable heat detector (detector here under) is a mated product of the 90 series fire alarm control panels. It uses a two-bus work mode. With an internal microprocessor, it supports electronic coding. The detector realizes real-time acquisition of the in-situ temperature data and sends back the data to a fire alarm control panel. It can also receive and execute the control commands given by a fire alarm control panel. When in a routing inspection, the detector indicator will blink. When there is a fire in the monitored area and the temperature has reached the alarm threshold, the fire alarm control panel will confirm a fire alarm according to the received message sent from the detector, and the detector indicator will light at the same time to indicate a fire alarm

The detector is suitable for such industrial and civil buildings that have a great deal of heat when fire takes place, such as kitchens, boiler rooms, generator rooms, drying workshops and smoking rooms and is not suitable for places with a great deal of smoke but little heat

II. Product features

It can realize electronic coding and rewrite the address via coder in-situ

Within a single-chip microcomputer, it can realize real-time data acquisition and processing, realize a curve tracing for the field situation

It has a temperature compensation function and a sensor fault detection function (fault reporting to fire alarm control panel)

Non-polarity, two-bus connection that ensures convenient installation and maintenance

Designed with an upper cover and a lower cover and installed on an independent base, it can be installed, debugged and maintained conveniently

III. Technical parameters

Executive standard: GB4716-2005
Operating voltage: 24V (pulse modulation)
Operating current: <300uA (monitoring status) or <1.5mA (alarm status)
Work indication: red indicator will blink in the monitoring status or remain lit in the alarm status
Weight: about 47g
Product class: A2
External dimensions: diameter: 100mm, height: 56mm (with the base)
Wiring method: non-polarity two-bus system (L1, L2)
Operating environment: indoor, temperature: - 10°C-+50°C, relative humidity: ≤95% (40°C±2°C, without condensation)
Coding mode: it can realize electronic coding via coder in-situ. Address codes 1 to 324 are available for selection.
Installation height: ≤8m

Protection area: about 60m2. For details, see related provisions in GB50116-98 Code for design of automatic fire alarm system
Matched host machine: fire alarm control panel (such as TP-AL7130)