Product parameters:

Product overview:
Transformer winding deformation testing (frequency response method) for testing 6KV And above voltage class of power transformers and other special-purpose transformers, power transformers in operation or during transport will inevitably suffer a variety of fault short-circuit current of shocks or physical impact, in the presence of strong electric short-circuit current transformer winding may lose stability, leads to distorted drum kit or permanent deformation phenomena such as displacement, which will seriously affect the safe operation of the transformer. According to the State electricity industry standards DL/T911- 2004Measurement of transformer winding deformation by frequency response analysis, through the detection of amplitude-frequency response characteristics of transformer windings, and the test results are vertical or horizontal comparison, according to the variability in the amplitude-frequency response characteristics, judge transformer winding deformation that may occur.
Transformer winding deformation testing (frequency response method) measurement and analysis of software components, measuring part is composed of signal generation and signal measurement of black boxes, analysis by the notebook computer, measuring part USB Or networks connected to the laptop.
Technical features:
l Not to hang the transformer cover and disassembly of case can be tested.
l Measuring the frequency sweeping method using the most popular.
l The instrument can be 6kV More than measuring transformers.
l Using split structure, between the host computer and the test host USB Connection, Plug and play.
l Field wiring is simple and easy to use.
l Wide dynamic range:- 100dB ~ 20dB.
l Powerful analysis software, the software, the hardware indicators meet the GB DL/T911-2004.
Technical specifications:
l Test host PC Interface: USB.
l Source: instrument comes with a channel signal output as a sweeping stimulus signals; Signal output for the standard sine wave signal output amplitude can be software, the most significant ±10VSignal output impedance 50Ω.
l Both acquisition channels, collecting signals, collected a response signal, is used to calculate the transfer function.
l Acquisition channels to quantify accuracy: 14People.
l Maximum storage capacity per channel: 64KSample points.
l Per-channel maximum sampling rate: 25Msps.
l Acquisition channel input impedance: 1MΩ.
l Sweep-frequency measurement range: 500Hz - 2000kHz.
l Scanning mode: linear sweep measurement mode of distribution.
l Scanning frequency accuracy: sine signal source output signals frequency accuracy is less than0.01%.
l Sweep measurement frequency: fixed or user-defined.
l Meet the national electric power industry standards: DL/T911-2004.
Test and analysis software key features:
l Using windows Platform compatibility Window 2000/Window XP.
l Can be loaded 2Curves, and curve parameters calculated automatically, automatic diagnosis of winding deformation, gives diagnostic conclusions.
l Software management is powerful and fully consider the needs of field use, environment condition parameters are automatically saved, provide a basis for better diagnosis of transformer winding deformation. Measured data is automatically saved, with color printing function, user-friendly test report.
l Software user-friendly features obvious, measuring all kinds of conditions for the selection, not in the field as a lot of input, more convenient to use.
l Software high intelligence, in the input and output signal connection ready, just press a button you can do all the work.
l Software interface is simple and intuitive.