SL-208-type underground cable jacket fault locator | safe and reliable

SL-208-type underground cable jacket fault locator | safe and reliable

1+
39800 CNY (5795USD)
3+
39790 CNY (5793.54USD)

add to cart

Product parameters:

  • Processing customization: Yes
  • Type: Communication detection instrument
  • Brand: Universal
  • Model: SL-208 type
  • Dimensions: 60 × 160 × 120
  • Weight: 0.9
  • Uses: To send a specific electromagnetic wave signal to the underground pipeline, the probe using the probe perpendicular to the ground plane tangent to the magnetic field lines, the received signal is minimal (almost




Warm Tip: The above prices are for reference only, please call or Want Want advice, thank you!





SL-208 underground cable jacket fault locator can not be excavated in the case of complex earth, convenient and accurate detection of the underground cable direction, buried depth and fault point is the power, communications sector and factories and mines can not The lack of equipment and right-hand man. By sending a specific electromagnetic wave signal to the underground pipeline, the detector probe perpendicular to the ground plane with the magnetic field lines when the received signal is small (almost zero) to determine the principle of the direction of the buried cable And depth.

'Features'
1. Small size, light weight, easy to carry;
2. Detection method is simple, easy maintenance, with automatic protection function;
3. Low power supply voltage, AC-DC dual-use, applicability;
4 transmitter power, high efficiency;
5. Detection error is small, anti-interference ability;
6. Stable and reliable performance, ability to adapt to the environment.


'Main Specifications'
(A) of the transmitter technical indicators:
1. Transmitting power: ≥25W, adjustable;
2. Transmitting frequency: 1K ± 0.1Hz, beat frequency 1-2Hz;
3. Output impedance matching: 0-100Ω;
4. Launch distance: ≤ 5Km (5 km can be moved step by step);
5 working current: ≤ 3A, 1-3A adjustable;
6. Working power: 12V (battery or car power);
7. Weight: 2.8Kg (excluding battery weight);
8. Overall dimensions: 99 × 220 × 220
(B) Detector Specifications:
1. Sensitivity: 0.1mV;
2. to the position deviation: < 20cm;
3. Detection depth: ≤ 5m;
4. Working power: 6V nickel-cadmium batteries;
5. Weight: 0.9Kg;
6. Overall dimensions: 60 × 160 × 120
(C) leak detector technical indicators:
1 leak detection accuracy: ≥ 0.35mm2;
2 Leak detection depth: ≤ 5m;
3 Positional deviation: < 30cm;
4 working power: 6V nickel-cadmium batteries;
5 Weight: 0.9Kg;
6 Overall dimensions: 60 × 160 × 120