Product parameters:
- Brand: JYINS / Elite
- Model: JYS-9S4
- Processing customization: Yes
- Measurement accuracy: 0.5,1.0 level
- Display: digital control
- Dimensions: 96 * 96
- Opening size: 91 * 91
- Measuring range: 999
- Size: 96 * 96
- Power supply voltage: AC / DC 80-270
Name: JYS-9S4 Multifunction Power Meter
Dimensions: 96x96 mm Hole Size: 91x91mm
General technical data
Accuracy class | 0.5, the frequency of 0.2 and |
Display method | Four, plus sign bit |
enter | Nominal input | Current | AC: Current 1A / 5A; |
Voltage | Voltage 100V / 220V / 400V |
Overloaded | Continuous: 1.2 times the instantaneous: voltage 2 times (1 second), current 10 times (5 seconds) |
frequency | 50Hz ± 10% |
power supply | Auxiliary power | Switching power supply: AC, DC80 ~ 270V, linear power supply: AC220V ± 5% |
Power consumption | <5VA |
Dielectric strength | AC2kV, 1 minute (the experimental voltage is AC rms) |
Insulation resistance | ≥100MΩ |
Mean time between failures (MTBF) | ≥60000 hours |
Working conditions | Ambient temperature: -10 ~ 55 ℃, relative humidity ≤ 95%, no corrosive gas place, altitude ≤ 2500m |
General shape and hole size
Shape code | Dimensions | Hole Size |
| A (mm) | B (mm) | C (mm) | D (mm) | E (mm) |
16 slot type | 158 | 78 | 140 | 151 | 71 |
42 Square | 120 | 120 | 80 | 111 | 111 |
6 Square | 80 | 80 | 76 | 76 | 76 |
5 slot type | 96 | 48 | 105 | 91 | 45 |
96 square | 96 | 96 | 78 | 81 | 81 |
72 Square | 72 | 72 | 74 | 67 | 67 |
Micro-square | 48 | 48 | 112 | 45 | 45 |
Use range
Control system, energy management system, substation automation, distribution network automation, building automation, industrial automation, residential power monitoring, intelligent building, switchgear and so on.
Precautions
1, before use, the instrument required power for 15 minutes.
2, pay attention to prevent vibration and shock, do not have excess dust and excessive use of harmful gases.
3, the input wire should not be too long Try shielded twisted pair cable, such as the signal input is longer.
4, if the signal is accompanied by high-frequency interference, should try online low-frequency filter.
5, long-term storage is not used, the power once every three months at least 4 hours.
6, long-term preservation should avoid direct sunlight, should be stored at an ambient temperature of -25 ° C ~ 55 ° C.
7, such as instrument no display, you should first check the auxiliary power supply, voltage is in the range.
8, such as the display is not normal, check the input signal is normal and the signal terminals are tightened.
9, unless the PT has enough power, or can not use the PT signal at the same time as an auxiliary power to ensure that the instrument work properly.
10, CT circuit current terminal screws must be tightened to ensure that the inlet / outlet access to reliable, in order to avoid failure.
11, to calibration instruments, calibration equipment should be better than 0.1 in order to ensure the calibration accuracy. (1)