Product parameters:


Product overview:
YD portable high current generator Is based on the electricity sector and industrial and mining enterprises in the electrical equipment such as switches, current transformers and other electrical equipment for the current load test and temperature-rise test and the design and manufacture of special equipment.
This small, lightweight one-piece structure, with stepless adjustment output current, current up balancing, load range, 0.5Class current transformers, digital display, appearance, reliable performance, easy operation, safety and so on. Is industrial and mining enterprises for up-flow or temperature-rise test ideal equipment.
Technical parameters
1And current generator rated capacity: KVA
2, voltage regulator rated capacity: KVA
3Input rated voltage: 220V
4Input rated current: 22.7A
5, Rated output current: 1000A
6Output voltage: 5V
7Impedance voltage: ﹤8%
8Idle current: ﹤6%
9And structure: one
Working principle:
1, the instrument must be well grounded.
2And pressed down into the power supply, switch on, red light is on, connect the outputs to test connections, press the Start button, green light is on, up waiting for current flow.
3Clockwise rotating with uniform pressure regulator, note counter output current indicates the high current required.
4, During the test, once found irregularities should immediately cut off the power supply, identify the cause of a test.
5, Test is complete, you must set the regulator back to zero, press the stop button cut off power supply, cut off the power supply , Removable test wiring, in order to ensure safety.
Notes:
1, New installations and transformer for a long time, before running 1500Measurement of megger between the coil and coil insulation resistance to ground, the resistance value of not less than 0.5When Meg, can be used.
2Using current transformers and operation must be reliably grounded to ensure safety.
3, Should slow even when using up-flow and handling should avoid excessive vibration.
4, Voltage regulator and brush contact surfaces should be kept clean, as the case 90%Alcohol-dipped cotton wipe clean.
5This equipment should be kept clean, well ventilated, dry and indoor save.
Complete sets of equipment:
1, Current transformer One
2, Product certification A share
3, The product usage manual A share
4Test report A share