Product parameters:



Manual
Use and applicable aspects:
Voltage, AC current, voltage, frequency, power factor, phase sequence, power, synchronization instructions and other non-electrical measurement.Mainly used in marine vessels, rail transit , The chemical explosion-proof, low-voltage equipment, construction equipment, generating units, machinery and equipment industries AC and DC transmission and distribution systems, power control panels and other electrical equipment. General requirements in the environmental conditions are more general in the high-end instruments.
Standards and Certification:
The instrument is in accordance with GB / T7676-1998, digital instrumentation is in accordance with GB / T22264-2008 standard production, the safety performance in accordance with GB4793 and IEC61010 standard production. Dial scale and pointer design in line with the German DIN43790 and DIN43802 standard. Meter shape and hole size in accordance with GB / T1242 and IEC61554 standard production. Elite Instrument Electric Company all products through the national CE certification, and access to IS0; 9001 certification.
Table shell aspects:
JY series The base is flame retardant TBT Made of plastic, Vicat temperature of 130 ℃. shell Made of flame-retardant ABS plastic, Vicat temperature 85 ℃.
The amount of change caused by temperature:
Reference temperature is 23 ℃ ± 2 ℃ .13 ℃ ~ 23 ℃ and 23 ℃ ~ 33 ℃ temperature range, the temperature change is not allowed to change the level index of ± 100%.
Installation location and installation methods:
Unless otherwise specified, the instrument is normally mounted in a vertical position Other installation positions such as horizontal installation and tilting installation can be made according to customer requirements The corresponding accuracy level is valid only for the specified installation position. °, two kinds of indication angle.
Anti-vibration and impact of impact:
Anti-vibration : In line with IEC60068-2-6 standard; sweep range: 10-55-10Hz; displacement amplitude: ± 0.15mm, ± 0.3mm.
Sweep frequency: 10ct / min; maximum acceleration: 147m / s2 (15g), 490m / s2 (50g).
Vibration acceleration time: 15min. Anti-mechanical shock, in line with IEC60068-2-27 standard.
Accuracy level:
JY series Pointer instruments: AC and DC voltmeter and ammeter in 1.5 or 2.5, power meter 2.5Level, the frequency table 2.5Level, power factor meter for the 2.5 level.
Overload ammeter aspects:
Overload times conventional 1 times and 2 times the overload factor, can be customized to 1 times the user requirements, 23 times, etc. Its role is to indicate the approximate instantaneous value of the overload current, such as the start-up current when the motor starts.
External current shunt side:
DC ammeter external shunt voltage drop specifications 150mV, 100mV, 75mV, 60mV and 50mV, etc. can be customized by the user requirements.~25mΩTo ensure instrument accuracy.
Surface Dial:
surface Dial: aluminum alloy, white paint, black ink printing or laser printing printing. Can be customized according to customer-like dial (customizable variety of colors overprint.) Luminometer dial with PC board.
Zero Regulator:
In addition to the mechanical zero reading instrument, the rest of all instruments are pre-zero regulator, used to adjust the instrument mechanical zero.
Advantages of the product (replaceable dial):
JY series AC meter as long as the transformer secondary current is the same, you can replace the dial, after replacement, the accuracy of the same; DC ammeter as long as the shunt output signal is the same or Instrument input terminal electrical signal the same, different specifications can replace the dial, after the replacement, the accuracy of the same.
The main technical parameters
Name | Code | Accuracy | Common specifications | Remarks |
AC ammeter | A | 1.5 | 0.5-50A | Directly connected |
AC ammeter | A | 1.5 | 10 / 5A-800 / 5A | Through the current transformer through the secondary current |
AC ammeter | KA | 1.5 | 1KA-10KA | The secondary current through the current transformer |
AC voltmeter | V | 1.5 | 10V-600V | Directly connected |
AC voltmeter | KV | 1.5 | 1KV-35KV | Through the voltage transformer secondary voltage 100V |
DC ammeter | ΜA mA | 2.5 | 50ΜA-500μA 1mA-500mA | Directly connected |
DC ammeter | A | 1.5 | 1A-15A | Directly connected |
DC ammeter | A | 1.5 | 15A-750A | 75mV.60mV.50mV can be extended to other non-power indicator, such as speed, rudder angle, temperature, pressure, etc. |
DC ammeter | KA | 1.5 | 1KA-3KA | 75mV.60mV.50mV can be extended to other non-power indicator, such as speed, rudder angle, temperature, pressure, etc. |
DC voltmeter | V | 1.5 | 3V-600V | Directly connected |
DC voltmeter | KV | 1.5 | 1KV-3KV | Then attached to the value of resistance |
Frequency table | Hz | 2.5 | 45-55HZ 55-65HZ | 36V.100V.127V.220V.380V |
power meter | KW.VAR | 2.5 | 100V 380V 380-380KV | Through the voltage transformer through the secondary voltage 100V through the current transformer secondary current 5-10KA / 5A |
Power factor meter | Cos Φ | 2.5 | COS Φ = 0.5-1-0.5 | 100V / 5A 220V / 5A 380V / 5A |
Three-phase synchronization table | S | 2.5 | 100V, 220V, 380 / 100V |
|
High - impedance table | MΩ | 1.5 | 0-5MΩ127V , 220V, 1mA | Head integration, with insulation monitor |
Power Grid Insulation Resistance Monitor | BMΩ | 2.5 | Measured below 500V, power, lighting 0-5MΩ | Integration, with alarm |
Dual display insulation resistance monitor | BMΩ | 2.5 | Measured below 500V, power, lighting 0-5MΩ | Integration, with alarm |
Synchronous table with parallel command | SM | 2.5 | Synchronization point 100V, 220V, 380V | Electronic luminous type 360 degrees |