Product parameters:
Zinc oxide arrester Tester Details:
, Profile:
Zinc oxide arrester electrified testing is one of the series of finished products of our factory is a comprehensive testing of MOA in power system operation the electrical characteristics of the instruments.
It has the following advantages:
1, liquid display text display, finished print, intuitive interface, high degree of automation, for field personnel to operate and use.
2, advanced digital signal processing technology, strong anti-jamming performance, high measurement accuracy, the user can observe signals directly from the LCD screen, with oscilloscope function.
3, safe and reliable, isolation transformers and high voltage, thus avoiding the PT secondary circuit.
4, small size, light weight, easy to carry.
Second, the technical characteristics:
1, power supply: AC 220V ± 50Hz ± 1%.
2, reference voltage input range: AC10~ 220V.
3, measurement parameters:
A, leakage current of arrester currents (including harmonics): I1, I3 I5 I7.
B, resistive leakage current (including harmonics): IR1 IR3 IR5 IR7.
C, resistive current peak is peak Ir+ peak Ir-
D, peak current: Ip
E, running (or testing) voltage (including harmonics): U1 U3 U5 U7
F, surge arresters-power: Pw
4, measurement accuracy: 5%
5, measuring range: leakage current: Ix = 0~ 10mA
Third, the test method:
(A) the online test:
Test circuit is shown in Figure 1. PT is being tested in phase of voltage transformers, MOV to be tested.
(B) the offline test:
Test circuit is shown in Figure 2. Wiring please take a 100 ω and 200 ω resistor string in MOA and the ground, to ensure that the test circuit connection.
Four steps:
Zinc oxide arrester electrified testing instrument panel layout in Figure 3.
(The tester has four buttons, General keys is: up arrow, down arrow key to select the corresponding menu section, verify that key and the exit button is used to modify the value or go to the next menu).
1, according to figure 1 or Figure 2 connect the test circuits, power on the tester.
2, mobile cursor to ' variable than entered ' document entered variable than, variable ratio is refers to run voltage (or test voltage) and access test instrument voltage channel of voltage signal of than, for Figure 1 wiring for PT of variable than, for Figure 2 wiring, is is test transformer of variable than, please note: for some has measurement winding of test transformer,, if voltage signal received in measurement winding Shang, is entered test voltage and measurement winding voltage of variable than.
3, move the cursor to the ' voltage ', correspond to voltage signal on channel select Panel.
4, move the cursor to ' full scale ' or ' fine '. ' Full scale ' is used to make simple measurements and tests for about 4 seconds. ' Fine ' is used for more complete testing, testing for about 15 seconds.
Press the confirm key to see the interface as shown in Figure 4:
Figure 4 voltage test voltage value, can be updated in real time, through this document, users can observe whether the test voltage, upon confirmation, the tester begins testing and results.
' Full scale ' output the results as shown in Figure 5
I1 is the total current value
IP for the peak current
Ir1 resistive current fundamental RMS
Ir+ resistive current positive peak
Ir-resistive current negative peak
U1 voltage fundamental value
PW for the active power:
In Figure 5 is displayed, press confirm button you will enter the printing data interface, press the three keys to repeat the test. ' Fine ' mode is split-screen shows all currents, voltages, resistive current fundamental and 3, 5, 7 and valid values. Peak current, resistive current of positive, negative peak and active power operation press the confirmation button to enter the next screen, press the exit key to return to the previous screen.
View the waveform using:
After you enter the variable ratio and voltage channel, move the cursor to ' view the waveforms ' a file press the confirm key to view the waveform of the voltage and current waveform can be refreshed in real time, when the waveform is displayed, there are several buttons can be used to read the waveform data.
1, press the up arrow key to move forward display data point by point.
2, press the down key to backward point-by-point display data.
3, press up + confirm key to fast forward displaying data.
4, fast backward press down + confirm key to display the data.
5, press the confirm key to continue the waveform display.
6, press exit to return to the main menu.
Five considerations:
1, the instrument must be earthed reliably to ensure that equipment and personal safety.
2, power test, should be in the low-voltage side of the sample (ground), a counter or 100-150 ω ω series resistor (testers have been given) and in the counter, or resistance to get I x signal, or may even make instruments with high voltage, do not use high pressure directly into the instrument, and test the low pressure side of transformer must be reliably grounded.
3, when the test line, use a multimeter confirmed Ix introduced the instrument between the wires in the conduction State in order to prevent high voltage circuit open circuit.
4, before entering the measurement, enter the ratio multiplier and voltage connections.
5, online tests, should be taken with PT signal arrester to be measured the same as the voltage reference signal. This tester the two voltage signals end is equipped with a 100mA fuse only, when the wrong connection causes short circuit, the fuse will blow up to guarantee the role of PT or test transformer, so when the tester displays testing voltage wrong, confirm the input ratio and voltage channel is correct, check if the insurance is burnt out.