Product parameters:


Function | Earth resistance measurement, voltage measurement, low value resistance measurement |
Power supply | DC 9V zinc-manganese dry battery R14S 1.5V 6; Continuous standby 300 hours |
Measurement mode | Third-line measuring precision, simple two-wire measurement |
Methods of measurement | Ground resistance: rated current pole method, measuring current is 3mA Max, 820Hz; Voltage: average value Rectifier |
Data mode | The average value, maximum value, minimum value |
Line resistance check | Avoid the test line is not fully inserted into the meter interface, or poor contact or user errors due to replace long test line, The grounding resistance measurement is more accurate. |
Display mode | 4-digit large LCD display, screen backlight, LCD size: 128mmx75mm; Display field: 124mmx67mm |
Measuring instructions | Measurement of blinking LED indicates, LCD counter display |
Grounding resistance | Range: ~ 2000 ω 0.01 ω; Resolution: 0.01 ω; Accuracy: ± 1%RDG ± 3dgt |
Ground voltage | Range: 0~ 600V AC; Resolution: 1V; Accuracy: ± 1%RDG ± 3dgt |
Meter size | High thickness: 215mmx190mmx95mm |
Test line | Section 3: Red 20m, yellow 10m, green 5M 1 |
Simple testing line | Article 2: the Red 1.6m, green 1.6m 1 |
Auxiliary grounding rods | 2 pieces: φ 10mmx150mm |
Measuring time | Voltage to ground: 3 times per second; Ground resistance: 5 seconds/second |
Measurement frequency | More than 5,000 times (10 ω 20 ω measurement, measuring 1, stop for 25 seconds and then test) |
Line voltage | Measure the voltage to ground: measurement of AC 600V |
RS232 interface | With RS232 interface, software control, stores can upload data into the computer, save the print |
Communication line | RS232 communication line 1, 1.5M |
Data storage | 400 group, flashes 'FULL ' Symbol indicates that storage is full |
Data retention | Data hold function: 'HOLD ' Symbol appears |
Data access | Data access functions 'READ ' Symbol appears |
Overflow display | Overrange overflow feature: 'OL ' Symbol appears |
Alarm function | When the measured value exceeds the alarm set point, the ' beep – beep – beep--' alarm |
Battery voltage | When the battery voltage drops to about 7.8V, the low battery voltage symbol ' ' appears, reminding battery replacement. |
Power consumption | Backlight: 25mA Max; Standby: 25mA Max (backlight off); Measurements: 70mA Max (backlight off) |
Quality | 1443g (including battery) |
Working temperature and humidity | -10 ℃ ~ 40 ℃; 80%RH the following |
Storage temperature and humidity | -20 ℃ ~ 60 ℃; 70%RH the following |
Overload protection | Ground resistance: E-P , E-C Each port AC 280V/3 seconds |
Insulation resistance | 10M or more (500V between circuits and shell) |
Pressure resistance | AC 3700V/rms (between circuits and housing) |
Electromagnetic properties | IEC61010-4-3, radio-frequency electromagnetic field ≤ 1V/m |
For safety | IEC61010-1, IEC1010-2-31, IEC61557-1,5, IEC60529 (IP54), pollution, 2, CAT III 300V |
Supplied accessories | Instrumentation: 1; Grounding pin: 2; Testing: 3; Simple test line: 2; RS232 communication cable: 1; Discs: 1; Instrument bag: 1 PCs |