CE Certified, Online High Frequency UPS, Ea900II, LVD, EMC, 120V/220V Available

CE Certified, Online High Frequency UPS, Ea900II, LVD, EMC, 120V/220V Available

bargain

add to cart
Model NO. EA900II 2KVA long back up model or standard model
Type On-line
Application Communication
Standby Time Long-acting Machine
Output Capacity Medium Type
Brand East
Specification CE, LVD, EMC
HS Code 850440
Phase Single Phase
Protection Overvoltage
Classification Online High Frequency UPS
Standby UPS Sine Wave Output UPS
Equipment Mode Standard Type or Long Back up Type
Trademark EAST, OEM
Origin Dongguan China
Online HF UPS EA900 II series 1kVA ~ 10kVA is EAST new generation UPS, we adopt the latest R & D achievements and application experience. With advanced DSP digital control technology, it improves performance& system reliability effectively, and achieves higher level of power density and miniaturization. Besides that, to meet all customer's individualized needs, as a high-end small power range online UPS, EA900 II can offer highly reliable power for departmental servers, small local area networks, workstations, industrial machines, small medical equipment, and other small precision electronic devicesic devicesc devices
Ideal Apllication
Centralized server center, mainframe, network control center, computing center
Features&Benefitsnefitsefits
High frequency and true double-conversion
DSP digital control technology
Input power factor correction (PFC)
Wide input voltage range (110V-300V)
Output power factor 0.9/0.8
Optimized Battery configuration
1K-24V/36V,2K-48V/72V,3K-72V/96V
Code start
Frequency adaptive
ECO mode operation for energy saving
Selectable output voltage via LCD
Output bypass settable for 1,2,3KVA via LCD
50Hz/60Hz frequency converter mode available on 6-10KVA
Selectable battery low voltage via LCD
Automatically diagnose when starts
Advanced battery management (ABM)
Short circuit and overload protection
Automatically charging battery at UPS off mode
Fan speed auto control when load varies
Standard RS232 communication port and RJ45 protection
Optional USB/SNMP communication port
Optional emergency power off (EPO)
Optional extension battery bank
Optional built-in isolation transformer
Optional manual bypass on 6-10KVA
Optional N+1 redundancy parallel on 6-10KVA
MODEL EA901II EA902II EA903II EA906II EA9010II
Capacity 1KVA/900W 2KVA/1800W 3KVA/2700W 6KVA/5400W 10KVA/9000W
INPUT
Rated Voltage 208V/220V/230V/240VAC
VoltageRange Half load (115-295)±5VACusmn;5VACsmn;5VAC
Full load (145-295)±5VACusmn;5VACsmn;5VAC
Half load (115-295)±5VACusmn;5VACsmn;5VAC
Full load (165-295)±5VACusmn;5VACsmn;5VAC
Frequency 45-55Hz±0.5%or 55-65Hz±0.5% (Auto Sensing)% (Auto Sensing) (Auto Sensing) 40-70Hz±0.5% (Auto Sensing) Sensing)Sensing)
Power Factor ≥0.98;0.980.98 ≥0.99;0.990.99
BypassVoltage Range Rated output voltage-34V ~ Rated output voltage+32V 160V ~ Rated output voltage+32V
OUTPUT
Voltage 208V/220V/230V/240VAC Setting available via LCD
Voltage Regulation ±1%plusmn;1%lusmn;1%
Frequency Synchronized with utility on AC mode;50/60±0.2Hz on battery modetery modeery mode
Waveform Pure sine wave
Crest Factor 3:1
Harmonic Distortion ≤3%(Linear load);≤5%(Non-linear load)ar load)r load) ≤2%(Linear load);≤5%(Non-linear load)ar load)r load)
Transfer Time AC mode to battery mode :0ms
Inverter model to bypass mode:4ms(Typical)
AC mode to battery mode :0ms
Inverter model to bypass mode:0ms
Overload Capability 105%-150%:Transfer to bypass after 30s;
﹥150%: Transfer to bypass after 300ms300ms
105%-125%:Transfer to bypass after 3mins;
125%-150%: Transfer to bypass after 30s;
﹥150%: Transfer to bypass after 100ms100ms
EFFICIENCY
AC Mode ≥90%e;90%;90% ≥92%e;92%;92%
BatteryMode ≥87%e;87%;87% ≥91%e;91%;91%
ECO Mode ≥98%e;98%;98% ≥98%e;98%;98%
BATTERY
DC Voltage 24V 36V 48V 72V 72V 96V 192V
Inbuilt Batteryof Standard Model 2*9Ah 3*7Ah 4*9Ah 6*7Ah 6*9Ah 8*7Ah 16*7Ah 16*9Ah
Charge Current Standard Model 1A
Long Time Model 6A 1A/3A/5A/8A
Typical Recharge Time 8 hours recover to 90% capacity
ALARM
Utility Failure Beep/4s
BatteryLow Beep/1s
Overload Beep Twice/1s
UPS Fault Long Beep
ENVIRONMENT
Humidity 20~90% RH @ 0~40°C(non-condensing)nsing)sing)
Noise Level ≤50dB (1m) (1m)(1m) ≤55dB (1m) (1m)(1m)
MANAGEMENT
Standard RS-232 ,Optional USB Supports Windows 98/2000/2003/XP/Vista/2008/7/8
Optional SNMP Power management from SNMP manager and web browser
PHYSICAL
Dimension(mm) W*D*H 144*357*215 144*410*215 190*452*341 190*470*341 190*452*341 190*470*341 262*514*455(H)
262*514*735(S)
Packing Dimension(mm) W*D*H 230*445*315 230*492*315 320*550*462 360*650*540(H)
360*650*795(S)
Net Weight(kg) 6.0(H)10.0(S) 6.5(H)13.0(S) 12.0(H)20.0(S) 13.0(H)25.0(S) 12.0(H)
24.0(S)
13.0(H)
29.0(S)
26.0(H)
67.0(S)
Gross Weight(kg) 7.0(H)11.0(S) 7.7(H)14.5(S) 13.3(H)21.5(S) 14.3(H)26.5(S) 13.3(H)25.5(S) 14.3(H)
30.5(S)
28.0(H)
78.0(S)