Modular UPS System 10KVA-200KVA (EA660 Series)

Modular UPS System 10KVA-200KVA (EA660 Series)

bargain

add to cart
Model NO. EA660 Series
Type On-line
Application Communication
Standby Time Long-acting Machine
Output Capacity Large Type
Brand East
Specification 10KVA-200KVA
HS Code 850440
Phase Three Phase
Protection Unbalanced Loads
Classification Lighting/Power
Standby UPS Sine Wave Output UPS
Equipment Mode Centralized Model
Trademark EAST
Origin China Mainland
Idea applications
IDC room, IT room, ISP server center, telecom, finance, securities, traffic. tax. medical system.
Features Introduction
Quick repair capacity
Traditional UPS are in maintenance bypass mode when they are in the service, load is not under protection, if any power failure occurs, or input fluctuations, , it may cause damage to the equipment. Meanwhile , equipment maintenance also need to go through a series of cumbersome procedures, system administrators need to notify the manufacturers, manufacturers rushed to the scene for maintenance with power off, system repairing time is uncertain due to several factors. When festivals or holidays, maintenance is difficulty, maintenance staff judgment maybe wrong, the customer site distance, all will take much time.
EA660 adopt new module hot swap technology, all modules supported plugging in and out. Power modules can be inserted or removed at any time online, power off operation is not required. If a power module fails, the module will automatically exit the system, the system won't be affected. When standby module arrives, take the faulty module out and insert the new module while UPS is working. Then restoration is completed, no power off or transfer to bypass, which achieved online maintenance for parallel system. These operations do not need specialized equipment and techniques.
Modular design
EA660 takes modular design, one module power is 20KVA/16KW, system consists of 1-20 modules and connected in parallel, the user can gradually increase the number of modules depending on the load. Between the module and the machine uses hot swap technology, UPS module can be inserted or removed online, enabling 0s downtime.
Flexible redundant parallel design
EA660 can be set up redundant UPS modules, and 0 can be set, when UPS can be a maximum capacity output. When the load exceeds the redundant design, as long as the amount power does not exceed the load module's total capacity, UPS can still work, and issue corresponding warnings.
Expansibility
Due to the fully modular design, the user can choose a appropriate capacity between 20KVA to 400KVA depending on the load, the configuration is very flexible. UPS system structure is very flexible. Power module design philosophy is to remove and replace the module at any time without affecting the operation of the system and output. Investment plans can be expanded as needed, allowing users to stick with the dynamic growth of business, meeting the requirement for post-equipment increase, also reducing the cost of procurement of pre-.
When users make estimation of UPS capacity, they often overestimated or underestimated
Availability
EA660 has superior features in parallel ,that are representative of the high-end UPS, mean time between failure MTBF is 1.5 times the traditional UPS, mean time between critical failures MTBCF is three times the traditional UPS, mean time to repair MTTR of traditional UPS is down 8 hours for maintenance, while EA660 maintenance in the system only requires 5 minutes, high availability shows the EA660 perfect protection and use of capacity ,which ensure the safety of the system and the load protection time increase exponentially.
Environmental protection
EA660 PFC circuit uses digital active power factor correction technology, the input current total harmonic distortion (THDI)is only 3%, while the input power factor ≥0.99, which greatly reduces the grid pollution, effectively reduce the power loss. Typically, the smaller the load, the lower the system efficiency. UPS actual load in data room usually are below 80%, even lower than 50%. When load is only 15%, efficiency of EA660 is more than 90% .When the load reaches 50%, the efficiency can be 93% or more. Even if the customer's load is small, system can achieve higher efficiency and cost will be saved for customers.ers.ers.

MODEL EA6680 EA66160 EA66200 EA66400
Capacity 20KVA-80KVA 20KVA-160KVA 20KVA-200KVA 20KVA-400KVA
Numbers of Parallel Module 1-4 1-8 1-10 1-20
Numbers of Redundancy Module 0-3 0-7 0-9 0-19
UPS Power Module 20KVA/16KW
INPUT
Rated Voltage 380V/400V/415VAC
VoltageRange 204-520VAC(Load≤50%);50%);0%);
242-520VAC(50%277V-520VAC(70%
Rated Frequency 50/60Hz Auto Sensing
FrequencyRange 40-70Hz
Power Factor ≥0.99;0.990.99
Total Harmonic Distortion (THDi) ≤3%le;3%e;3%
BypassVoltage Range Rated output voltage-40%- Rated output voltage+20%(Setting available via LCD)
OUTPUT
Voltage 380V/400V/415VAC
Voltage Regulation ±1%plusmn;1%lusmn;1%
Frequency Synchronized with utility on AC mode;
50/60Hz±0.1%on battery modetery modeery mode
Waveform Pure sine wave
Crest Factor 3:1
Total Harmonic Distortion(THDV) ≤1%(Linear load);≤3%(Non-linear load)ar load)r load)
Transfer Time AC mode to battery mode :0ms
Inverter mode to bypass mode:0ms
Inverter Overload Capability 110%-130%:Transfer to bypass after 10mins;
130%-150%:Transfer to bypass after 1mins;
﹥150%: Transfer to bypass after0.5sr0.5s
Bypass Overload Capability ≤150%: Long time runningnningning
﹥150%: Power off after 10sr 10s
BATTERY
DC Voltage ±240V(Option:±190V/±204V/±215V/±228V)lusmn;204V/±215V/±228V)±228V)lusmn;204V/±215V/±228V)
Inbuilt Batteryof Standard Model 40*12V/9AH for each module
Charger Current 1-30A/60A(Setting available via LCD) 1-60A/120A (Setting available via LCD)
SYSTEM
Efficiency ≥93%e;93%;93%
Display Panel 5.7 Inches LCD touch screen
Alarm Battery mode, Battery voltage low, Fans fault etc
Maximum Parallel numbers 2
EMI EN62040-2
EMS IEC61000-4-2(ESD)
IEC61000-4-3(RS)
IEC61000-4-4(EFT)
IEC61000-4-5(Surge)
ENVIRONMENT
Humidity 0~95% RH @ 0~40°C(non-condensing)nsing)sing)
Noise Level ≤60dB;60dB60dB
MANAGEMENT
Communication RS232,RS485,USB,Dry contact
Supports Windows 98/2000/2003/XP/Vista/2008/7/8
Optional SNMP Power management from SNMP manager and web browser
PHYSICAL
Module Dimensions(mm) W*D*H 482*590*131
Module Weight 28kg/Power module , 27kg/Charger module ,7kg/Monitor module
UPS Dimension(mm) W*D*H 600*1000*1600 600*1000*2000 1200*1000*2000
UPS Packing Dimension(mm) W*D*H 700*1070*1760 700*1070*2160 700*1070*2160(×2)times;2)imes;2)
UPS Net/Gross Weight(kg)
Without Inbuilt Battery and Power Module
225/245 290/310 280/300 560/600
Input/Output/Bypass breaker Yes Yes No No