1-3kVA Online High Frequency UPS (EA901II, EA902II, EA903II)

1-3kVA Online High Frequency UPS (EA901II, EA902II, EA903II)

bargain

add to cart
Model NO. EA901II, EA902II, EA903II
Type On-line
Standby Time Long-acting Machine
Brand East
Specification EMC50091, 9254
Phase Single Phase
Protection Overcurrent
Standby UPS Sine Wave Output UPS
Trademark EAST, OEM
Online HF UPS EA900 II series 1kVA ~ 10kVA is EAST new generation UPS, we adopt the latest R & D achievements and application experience. With advanced DSP digital control technology, it improves performance& system reliability effectively, and achieves higher level of power density and miniaturization. Besides that, to meet all customer's individualized needs, as a high-end small power range online UPS, EA900 II can offer highly reliable power for departmental servers, small local area networks, workstations, industrial machines, small medical equipment, and other small precision electronic devicesic devicesc devices
Ideal Apllication
Centralized server center, mainframe, network control center, computing center
Features&Benefitsnefitsefits
Adopt DSP digital control technology
Adopt advanced DSP digital control technology, it improves performance& system reliability effectively, and achieves higher level of power density and miniaturization.tion.tion.
Besides that, it can meet all customers's individualized needs, EA900 II Series 1 ~ 10kVA provide very rich extensible function, users can configure the need flexibly
Output power factor 0.8
PF 0.8 is more suitable for the trend of electrical equipment, and can take more load. With new ECO (Economic) function, system efficiency can achieve 95%, it lower UPS power consumption and save user's cost.
Input PFC
Adopt digital control input PFC technology, Input Power Factor can be more than 0.98, it avoids pollution to power grid, saves energy, and also reduces cost
Digital Control at DC-DC Converter
EA900II 1~3kVA UPS adopt digital control, use Digital Control at DC-DC converter part instead of Analog Control in the past, and it is more reliable.
Green Environment-Friendly Model
EA900II is green model; Comply with RoHS and National Electronics Pollution Management Solutions. Under normal using, it will not cause harm to human and environment
Wide input voltage range
Extremely wide input voltage and frequency range, even in very poor power environment of the remote areas can normally supply the power. It reduced the frequency of battery discharge so that the battery life can be prolonged.
The UPS contain I/P and O/P over-protection, short voltage protection, overload protection, short-circuit protection, inverter over-heat protection, battery low voltage warning protection and battery overcharge protection, etc. Which is the above greatly ensure the stability and reliability of running the system.
Perfect Protection
With bypass function, when the output overload or UPS failure, can turn to bypass without interruption, and supply power to load by mains supply, accordingly provide alarm information.
With input L and N lines detective function, can prevent the danger caused by the inversion of L and N lines.
Cold start and mains power start function.
For emergency status, UPS can start with battery directly when the mains power anomalies.
UPS can start directly without battery; Can be used for high precision stabilizer
Can be used with generator
Wide range of input voltage and frequency, that can effectively isolate the adverse power from generator, can provide clean, safe and stable power supply the load.
Zero switching
Double-conversion online design, that can tracking frequency, phase locked, stable voltage, filter noise, prevent mains interference for UPS output, let the UPS become pure sine wave power supply, to provide more comprehensive protection for the load. Transfer time is zero when the mains power unstable, it can ensure safety and reliability for the load operation
Intelligent Battery Management
It adopts intelligent management technology to charge by three steps, to effectively extend battery life and reduce the number of battery maintenance.
Friendly interface
Powerful extensibility features
Smart slot can provide a wealth of scalable features, you can choose to install UPS smart 2000 monitoring card, SNMP card, RS485, AS400 card, EMD environmental monitor.
Technical Specification:
Model EA901II EA902II EA903 II EA906II EA9010 II
Capacity 1KVA 2KVA 3KVA 6KVA 10KVA
INPUT
Rated input voltage 220V
Rated input frequency 50Hz/60Hz (self-adaption )
Input voltage Range 110~300 VAC (Half load), 140~300VAC (Full load)
Input frequency Range 45-55Hz +/-0.5% 50Hz
55-65Hz +/-0.5% 60Hz
Phase single phase+N+GND
Power factor ≥ 0.98 0.980.98 ≥ 0.99 0.990.99
Input current (liner full load) 4.0A 8.1A 12.1A 24.2A 40.4A
THD < 5%
ByPass voltage range 186VAC-252VAC
OUTPUT
Rated voltage 208VAC/220VAC/230VAC/240VAC can be set on LCD
Power factor 0.8
Voltage distortion ± 2%lusmn; 2%usmn; 2%
DC component voltage ≤ 200mv200mv00mv
Output current crest factor 3: 01
Rated frequency
AC mode same as input frequency
Battery mode 50/60± 0.2Hzmn; 0.2Hzn; 0.2Hz
Phase lock speed ≤ 1Hz/s1Hz/sHz/s
Wave distortion 100% linear load < 3%; 100%; nonlinear load < 5% < 5%
Transfer time
From Mains mode to battery mode 0ms
From battery mode to Mains mode 0ms
From Mains mode to bypass mode < 4ms; 4ms
From bypass mode to Mains mode < 4ms; 4ms
From normal mode to ECO mode ≤ 10ms 10ms10ms
System Efficiency Full load ≥ 90 % 90 %90 % ≥ 92%; 92% 92%
ECO mode ≥ 94%; 94% 94%
Inverter overload capacity 105%~150% 30s transfer to bypass mode giving alarm;
﹥ 150% 300ms transfer to bypass mode giving alarm;larm;
Battery
Battery type Lead Acid maintenance free battery
DC voltage 24V DC 48V DC 72V DC 168V DC 168V DC
Inbuilt battery 7AH/12V 7AH/12V 7AH/12V 9AH/12V 9AH/12V
Battery quantity 2 4 6 14 14
Charge
Output voltage 27.5± 0.4Vsmn; 0.4Vmn; 0.4V 55± 0.6Vsmn; 0.6Vmn; 0.6V 82.5± 0.9Vsmn; 0.9Vmn; 0.9V 193.7± 0.9Vsmn; 0.9Vmn; 0.9V 193.7± 0.9Vsmn; 0.9Vmn; 0.9V
Charge method Three-stage charging
Recharge time 90% capacity after 5hrs charging (standard model)
According to battery capacity(long time model)
Input voltage range 80VAC~300VAC
Charge current Standard model: 1A
Long time model: 6A
(can extend to 12A)
Protection
Over-temp protection
Fan testing protection
AC L and N connect wrong protection
Output short circuit protection
Control
Silence; cold start; AC restart; Auto restart.
Communication
RS232, SNMP card, USB
Software function
Statue analyze: Switch on/off UPS system, Monitor UPS working state, store history
Display LCD/LED
System Operating Environment
Operating environment Operation tem. 0 ~ 40 degree centigrade
Store tem. -25 ~ 55 degree centigrade
Humidity 20 ~ 90%(non-condensing)
Altitude 0m< altitude < 1500m, over 1500m,r 1500m,
used with power derated
Noise < 50db (1-3kva)3kva)
< 55db(6-10kva)0kva)
Dimension(W*D*H) 357*144*215 439*190*341 439*190*341 514*262*455
(Long time model)
574*262*710
(Standard model)
Weight(Kg) Long time model 6 12 12.5 42
Standard model 10 20 24 57