200kVA Online UPS Low Frequency Three Phase for Medical

200kVA Online UPS Low Frequency Three Phase for Medical

10500-125000 USD

add to cart
Model NO. GL33 200kva
Type On-line
Application Industry
Standby UPS Sine Wave Output UPS
Equipment Mode Centralized Model
Input Voltage 380V400/415VAC
Transfer Time 0 Ms
Warranty 12 Months
Transport Package Cartons
HS Code 8504402000
Phase Three Phase
Protection Over Voltage / Short Circuit
Standby Time Long-acting Machine
Output Capacity Large Type
Features Isolated Transformer
Power Efficiency 0.9
Battery Type Sealed Lead Acid Maintenance-Free Battery
Trademark STCB
Origin Guangzhou Shenzhen
200kVA Online UPS Low Frequency Three Phase for medical
Main Features:
1. Online double-conversion
2. DSP technology guarantees high reliability
3. True galvanic isolation transformer design
4. Control designed to withstand all kinds of loads
5. Intelligent battery management to prolong battery lifecycle
6. Redundant fan design and independent ventilation enhance durable operation under
harsh environment

7. Adjustable battery numbers
8. Accept dual-mains input
9. Parallel operation with up to 4 units (option)
10.Variety of communication options available
Product description:
The On-Line-Series is an uninterruptible power supply incorporating
double-converter technology. It provides perfect protection specifically for
strict load.
The double-converter principle eliminates all mains power
disturbances. A rectifier converts the alternating current from the socket
outlet to direct current. This direct current charges the batteries and powers
the inverter.
In the event of power failure, the maintenance-free batteries
power the inverter. Thus the inverter generates a sine wave AC power,
which permanently supplies the loads.
Designed with the proven on-line, double conversion architecture, this
series of UPS offers the greatest degree of availability in power protection
and provides continuous high-quality AC power to connect strict load,
especially for the basic equipments in some areas as: finance,
communication, government, traffic, manufacture, education and so on.

Additionally The UPS provides abundant interfaces such as RS232, SNMP, AS400, and RS485 for supervision and configure.

Specification:
Model GL33 10K GL33 15K GL33 20K GL33 30K GL33 40K GL33 60K GL33 80K GL33 100K GL33 120K
CAPACITY 8 KW 12 KW 16 KW 24 KW 32 KW 48 KW 64 KW 80 KW 96 KW
INPUT
Nominal Voltage 3 x 380VAC/400VAC (3Ph + N)
Acceptable Voltage Range 305VAC ~ 460VAC
Frequency 50/60 Hz ± 10 %mn; 10 %mn; 10 %
INVERTER
Nominal Voltage 3 x 380VAC/400VAC (3Ph + N)
Precision Stationary: ±1% ; Transitory: ±5% (load variations 100-0-100%)ons 100-0-100%)ons 100-0-100%)
Frequency 50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz ±0.1 Hz;0.1 Hz ±0.1 Hz
Max. Synchronisation Speed ±1 Hz/sn;1 Hz/sn;1 Hz/s
Waveform Pure Sinewave
Total Harmonic Distortion (THDv) < 2% (Linear Load) ; < 5% (Non-linear Load)r Load)
Phase Displacement 120º ±1% (balanced load) ; 120º ±2% (imbalances 50% of the load)balances 50% of the load)balances 50% of the load)
Dynamic Recovery Time 3 cycles at 98 % of the static value
Admissible Overload 110% for 10min; 150% for 60sec ; ﹥160% for 200ms00ms
Admissible Crest Factor 3:1
Admissible Power Factor 0.6~1 (inductive or capacitive)
Imbalance Output Voltage
@ 100% Unbalanced Load
<1%
Current Limit High overload, short-circuit: RMS Voltage Limit ; High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS
Type Solid state
Voltage 3 x 380VAC/400VAC (3Ph + N)
Frequency 50/60 Hz
Activation Criterion Microprocessor control
Transfer Time Zero
Admissible Overload 150% for 1 hour; 180% for 30sec; ﹥200% for 200ms00ms
Transfer to Bypass Immediate, for overloads above 160%
Retransfer Automatic after alarm clear
MAINTENANCE BYPASS
Type Without interruption
Voltage 3 x 400V (3Ph + N)
Frequency 50/60 Hz
Overall Efficiency
(Line mode)
Line Mode 90% 91% 92% 93%
Battery Mode 90% 91% 93% 93%
BATTERY & CHARGERARGERARGER
Battery Type and Numbers 12VDC x 32 pcs (29~32 pcs adjustable)
Nominal Battery Voltage 384 VDC (Based on 32pcs batteries)
Charging Method CC/CV
Charging Current Default 10A, Max. 7= Capacity / Battery Voltage Default: 10A. Max. 40A
Charging Voltage 432 VDC (Based on 32pcs batteries)
PHYSICAL
Dimension
D x W x H (mm)
656*405*817 656*405*941 821*432*1159 975*554*1286 975*635*1326
Net Weight (kgs) 118 120 179 241 278 400 471 573 650
* Product specifications are subject to change without further notice
Company and factory:
Project and Trade show:
Our services:

1. OEM&ODM services acceptable.able.able.

2. 1% pcb board provided .

3. Lots of cooperated agent for shipping by sea or by air.

4. 1year warrenty , if it is quality problem , we will provide the parts for free .

FAQ:

Q1: Why you should choose us?

---16 years UPS experiences

---Professional team for both oversea and domestic market

--UPS provider of SCO meeting 2015 and Shanghai-Kunming high-speed railway project

---Qualified product plus competitable prices

---Delivery in time

---Sincerely services

Q2: How is your after-sale service?

---We provide 12-24 months warranty since the delivery date and free maintenance /

replacement during warranty period.

Q3: What kind of certification you have?

---ISO9000, CE,ROHS,UL,and so on

Our products could pass different labor testing according to different countries' requirements.

Q4: Delivery time:

---Standard products could be delivered within 15 days; customized products could be

developed within 45-60days.