| Model NO. | GR11 6kva 10kva |
| Type | On-line |
| Standby Time | Long-acting Machine |
| Output Capacity | Medium Type |
| Power Capacity | 4800W/8000W |
| Power Factor | 0.9 |
| External Battery Pack | Support |
| Transport Package | Cartons |
| HS Code | 8504402000 |
| Phase | Single Phase |
| Protection | Short Circuit |
| Standby UPS | Sine Wave Output UPS |
| Product Feature | Rack Mount |
| Transfer Time | 0 Ms |
| Package | Standard Cartons |
| Trademark | STCB/Neutral |
| Origin | Guangzhou Shenzhen |
| Model | GR11-6K(L) | GR11-10K(L) | |
| Capacity | 6KVA/4800W | 10KVA/8000W | |
| Input | Nominal Voltage | 208/220/230/240VAC | |
| Voltage Range | 110-300VAC±3% at 50% load50% load50% load 176-300VAC±3% at 100% load100% load00% load | ||
| Frequency | 40-60Hz/50-70Hz | ||
| Power Factor | 0.99 | ||
| Output | Voltage | 208/220/230/240VAC | |
| Voltage Regulation | ±1%lusmn;1%lusmn;1% | ||
| Frequency Range (Synchronized Range) | 46-54HZ or 56-64HZ | ||
| Frequency Range (Batt. Mode) | 50HZ±0.1HZ or 60HZ±0.1HZHZ±0.1HZn;0.1HZHZ±0.1HZ | ||
| Current Crest Ratio | 3:1 | ||
| Harmonic Distortion | ≤3% THD(Linear load) ≤6% THD(Non-linear load)r load)r load) | ||
| Transfer Time | 0ms | ||
| Wave Form | Pure Sinewave | ||
| Efficiency | AC Mode | 89% | 90% |
| Battery Mode | 88% | 89% | |
| Battery (Standard Model) | Battery Type | 12V7AH | 12V9AH |
| Numbers | 16PCS | 16PCS | |
| Typical Recharge Time | 9 hours recover to 90% capacity | ||
| Charging Current | Default:1.0 A ± 10%, Max.:2.0A ± 10%0A ± 10%mn; 10%0A ± 10% | ||
| Charging Voltage | 218.4 VDC ± 1%usmn; 1%usmn; 1% | ||
| Battery (Long-run Model) | Battery Type | Depending on the capacity of external batteries | |
| Numbers | 16-20** (adjustable) | ||
| Charging Current | Default:4.0 A ± 10%, Max.:6.0A ± 10%0A ± 10%mn; 10%0A ± 10% | ||
| Charging Voltage | 273 VDC ± 1% (based on 20 pcs batteries)tteries)tteries) | ||
| Indicators | LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |
| Alarm | Battery Mode | Sounding every 4 seconds | |
| Low Battery | Sounding every second | ||
| Overload | Sounding twice every second | ||
| Fault | Continously sounding | ||
| Physical (Standatd Model) | Dimension (mm) | UPS Unit:500*438*88(2U) Battery pack:668*438*88(2U) | UPS Unit:580*438*133(3U) Battery pack:668*438*88(2U) |
| Net Weight(kgs) | UPS Unit:15 Battery Pack:40 | UPS Unit:18 Battery Pack:48 | |
| Physical (Long-run Model) | Dimension (mm) | 500*438*88 (2U) | 580*438*133(3U) |
| Net Weight(kgs) | 15 | 18 | |
| Environment | Humidity | 0-95 % RH @ 0- 40°C (non-condensing)sing)sing) | |
| Noise Level | Less than 55dBA @ 1 Meter | Less than 58dBA @ 1 Meter | |
| Management | Smart RS232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC | |
| Optional SNMP | Power management from SNMP manager and web browser | ||