| Model NO. | GR11 3KVA |
| Type | On-line |
| Application | Computer Server |
| Standby UPS | Sine Wave Output UPS |
| Product Feature | Rack Mount |
| Power Capacity | 2400W |
| Power Factor | 0.99 |
| Charge Period | 8 Houres to 90% |
| Warrenty | 1 Year |
| Transport Package | Cartons |
| Origin | Guangzhou Shenzhen |
| Phase | Single Phase |
| Protection | Short Circuit |
| Standby Time | Standard Machine |
| Output Capacity | Small Type |
| Physical | 19 Inches 2u |
| Transfer Time | 0 Ms |
| Charge Current | 1A |
| Backup Time | 15 Minutes Full Load |
| Trademark | STCB |
| Specification | 630*438*88mm |
| HS Code | 8504402000 |

| Model | GR11-1K(L) | GR11-2K(L) | GR11-3K(L) | |
| Capacity | 1KVA/800W | 2KVA/1600W | 3KVA/2400W | |
| Input | Nominal Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | ||
| Voltage Range | 55-145VAC or 110-300VAC at 50% load 85-140VAC or 160-280VAC at 100% load | |||
| Frequency | 40-60Hz / 50-70Hz | |||
| Power Factor | 0.99 | |||
| Output | Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | ||
| Voltage Regulation | ±1%lusmn;1%lusmn;1% | |||
| Frequency Range (Synchronized Range) | 47-53HZ or 57-63HZ | |||
| Frequency Range (Batt. Mode) | 50HZ±0.25HZ or 60HZ±0.3HZHZ±0.3HZn;0.3HZHZ±0.3HZ | |||
| Current Crest Ratio | 3:1 | |||
| Harmonic Distortion | ≤3% THD(Linear load) ≤6% THD(Non-linear load)r load)r load) | |||
| Transfer Time | 0ms | |||
| Wave Form | Pure Sinewave | |||
| Efficiency | AC Mode | 88% | 89% | 90% |
| Battery Mode | 83% | 87% | 88% | |
| Battery (Standard Model) | Battery Type | 12V9AH | 12V9AH | 12V9AH |
| Numbers | 2PCS | 4PCS | 6PCS | |
| Typical Recharge Time | 4 hours recover to 90% capacity | |||
| Charging Current | 1A | |||
| Charging Voltage | 27.4VDC ± 1%usmn; 1%usmn; 1% | 54.7 VDC ±1%lusmn;1%lusmn;1% | 82.1 VDC ±1%lusmn;1%lusmn;1% | |
| Battery (Long-run Model) | Battery Type | Depending on the capacity of external batteries | ||
| Numbers | 3 | 6 | 8 | |
| Charging Current | 1.0A/2.0A/4.0A/6.0 A | |||
| Charging Voltage | 41.0VDC ± 1%usmn; 1%usmn; 1% | 82.1 VDC ±1%lusmn;1%lusmn;1% | 109.4VDC ±1%lusmn;1%lusmn;1% | |
| Indicators | LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | ||
| Alarm | Battery Mode | Sounding every 4 seconds | ||
| Low Battery | Sounding every second | |||
| Overload | Sounding twice every second | |||
| Fault | Continously sounding | |||
| Physical (Standatd Model) | Dimension(mm) | 310*438*88(2U) | 410*438*88(2U) | 630*438*88 |
| Net Weight(kgs) | 12 | 19 | 29.3 | |
| Physical (Long-run Model) | Dimension,D*W*H(mm) | 310*438*88(2U) | 410*438*88(2U) | |
| Net Weight(kgs) | 9 | 12 | 14.2 | |
| Environment | Humidity | 20-90 % RH @ 0- 40°C (non-condensing)sing)sing) | ||
| Noise Level | Less than 50dBA @ 1 Meter | |||
| Management | Smart RS232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC | ||
| Optional SNMP | Power management from SNMP manager and web browser | |||