Model | GSA220-10K3 | GSA220-20K3 | GSA220-30K3 | GSA220-40K3 | GSA220-50K3 | GSA220-60K3 |
| Rated output power | 8KW | 16KW | 24KW | 32KW | 40KW | 48KW |
| Battery input |
| Battery model | Lead acid battery |
| Rated voltage(VDC) | 220.0 |
| Float voltage (VDC) | 243.0 |
| Bulk voltage(VDC) | 255.6 |
| PV input |
| Controller model | MPPT |
| Max input power(kW) | 12.7 | 25.5 | 38.1 | 50.1 | 63.5 | 76.5 |
| Max input current(A) | 50 | 100 | 150 | 200 | 250 | 300 |
| Recommend working current(VDC) | 330 |
| Working voltage range(VDC) | 250-450 |
| Max input voltage(VDC) | 460 |
| Mains bypass (optional) |
| Input voltage range(Vac) | 380±15%usmn;15%usmn;15% |
| Input frequency(Hz) | 50/60±3%lusmn;3%lusmn;3% |
| Mains charging current (optional) | Standard:10A |
| AC output |
| Output wave | Pure sine wave |
| Output voltage | 380VAC±1%lusmn;1%lusmn;1% |
| Output frequency (Hz) | 50/60±1%lusmn;1%lusmn;1% |
| Output wave distortion(THD) | ≤3%(liner overload)oad)oad) |
| Inverter efficiency (80% resistive load) | ≥90%;90%;90% |
| Current peak factor | 3:1 |
| Overload capacity | 105-110%,600Secs;110-125%,60Secs;﹥125%,1SecsSecs |
| Display | LCD+LED |
| Protection | Input reverse polarity protection, input under-voltage protection, input overvoltage protection, output overload protection, output short circuit protection (no automatic recovery, you need to restart the machine), overheating protection. |
| Commutation | RS485(optional) |
| Environment demands |
| Protection | IP20 |
| Altitude (m) (m) | ≤4000(Every 100m decreases 1% 1000m+)0m+)0m+) |
| Cooling | Forced air |
| Relative humidity | <95% non-condensingsing |
| Temperature(ºC)rdm;C)rdm;C) | -10~+50 |
| Noise(1m) | ≤60dB60dB60dB |
| Dimension(D x W x H) mm | 840x480x1230 | 840x480x1230 | 600x800x1600 | 600x800x1600 | 600x800x2000 | 600x800x2000 |
| Weight(Kg) | 230 | 300 | 350 | 460 | 550 | 760 |