| ZRN-LWGY • | • •• | • | • | • | Description | ||||
| class type | ZRN-LWGYA | Flow sensor pulse output three-wire, + 12V power supply; | |||||||
| ZRN-LWGYB | Site display type 3V battery-powered; | ||||||||
| ZRN-LWGYC | Site display with 4 ~ 20mA or pulse output, + 24V power supply; | ||||||||
| ZRN-LWGYD | Flow Transmitter 4 ~ 20mA output, + 24V power supply; | ||||||||
| public Say through path | 4 | Normal flow range m3/h | 0.04~0.25 | Extended flow range m3/h | 0.04~0.4 | ||||
| 6 | 0.1~0.6 | 0.06~0.6 | |||||||
| 10 | 0.2~1.2 | 0.15~1.5 | |||||||
| 15 | 0.6~6 | 0.4~8 | |||||||
| 20 | 0.8~8 | 0.45~9 | |||||||
| 25 | 1~10 | 0.5~10 | |||||||
| 32 | 1.5~15 | 0.75~15 | |||||||
| 40 | 2~20 | 1~20 | |||||||
| 50 | 4~40 | 2~40 | |||||||
| 65 | 7~70 | 3.5~70 | |||||||
| 80 | 10~100 | 5~100 | |||||||
| 100 | 20~200 | 10~200 | |||||||
| 125 | 25~250 | 12.5~250 | |||||||
| 150 | 30~300 | 15~300 | |||||||
| 200 | 80~800 | 40~800 | |||||||
| Anti burst | Without marking, non-explosion-proof | ||||||||
| B | Explosion-proof | ||||||||
| Accuracy grade | A | Accuracy 0.2 | |||||||
| B | Accuracy 0.5 | ||||||||
| C | Accuracy 1.0 | ||||||||
| turbine Types of | A | Normal flow range | |||||||
| B | Extended flow range | ||||||||
| Explanation: DN4 ~ DN10 diameter threaded or welded, equipped with front straight pipe and filters, a maximum pressure of 6.3MPa. DN15 ~ DN40 diameter sensor is threaded connection, the pressure is 2.5MPa. DN50 ~ DN200 diameter sensor flange connection, pressure is 1.6Mpa. DN15 ~ DN40 diameter Optional Front and rear with a straight pipe or union, carbon steel and stainless steel materials. For DN15 ~ DN40 diameter flange connections, when ordering. • high pressure type and special requirements when ordering. | |||||||||
| Meter diameter and connections | 46101520253240 threaded connection |
| (1520253240) 506580100125150200 flange connection | |
| Accuracy class | ±0.5%R |
| Turndown ratio | 1: 10; 1: 15; 1: 20 |
| Meter Materials | 304, 316 (L) stainless steel |
| Measured medium temperature (℃) | -20~+120℃ |
| Environmental conditions | Temperature -10 ~ + 55 ℃, relative humidity of 5% to 90%, atmospheric pressure 86 ~ 106Kpa |
| output signal | 4-20mADC current signal (LWGY- • C type) |
| Power supply | LWGY- • B type: Built-in lithium battery (can be used continuously for 3 years); LWGY- • C type: + 24VDC |
| Signal transmission lines | 2 * 0.3 (two-wire) |
| Transmission distance | ≤1000m |
| Signal line interface | Internal thread M20 * 1.5 (LWGY- • C type) |
| Explosion levels | ExdIIBT6 |
| Protection class | IP65 |
| Meter diameter (mm) | Normal flow range (m3/h) | Extended flow range (m3/h) | Conventional withstand pressure (MPa) | Special voltage level (MPa) (flange connection) |
| DN 4 | 0.04~0.25 | 0.04~0.4 | 6.3 | 121625 |
| DN 6 | 0.1~0.6 | 0.06~0.6 | 6.3 | 121625 |
| DN 10 | 0.2~1.2 | 0.15~1.5 | 6.3 | 121625 |
| DN 15 | 0.6~6 | 0.4~8 | 6.32.5 (flange) | 4.06.3121625 |
| DN 20 | 0.8~8 | 0.45~9 | 6.32.5 (flange) | 4.06.3121625 |
| DN 25 | 1~10 | 0.5~10 | 6.32.5 (flange) | 4.06.3121625 |
| DN 32 | 1.5~15 | 0.8~15 | 6.32.5 (flange) | 4.06.3121625 |
| DN 40 | 2~20 | 1~20 | 6.32.5 (flange) | 4.06.3121625 |
| DN 50 | 4~40 | 2~40 | 2.5 | 4.06.3121625 |
| DN 65 | 7~70 | 4~70 | 2.5 | 4.06.3121625 |
| DN 80 | 10~100 | 5~100 | 2.5 | 4.06.3121625 |
| DN 100 | 20~200 | 10~200 | 2.5 | 4.06.3121625 |
| DN 125 | 25~250 | 13~250 | 1.6 | 2.54.0 |
| DN 150 | 30~300 | 15~300 | 1.6 | 2.54.0 |
| DN 200 | 80~800 | 40~800 | 1.6 | 2.54.0 |