• Unimpeded flow measurement tube parts, so there is no additional pressure loss ; Measuring the pipe no moving parts, so very long sensor life.
• Since the induced voltage signal is in the whole space is filled with a magnetic field formed, is the average of the surface pipe set, so the sensor straight pipe required for a shorter length of 5 Times the pipe diameter.
• Only part of the sensor lining and electrode in contact with the measured liquid, as long as a reasonable choice of electrode and lining material can be resistant to corrosion and wear resistance.
• ZRN-LDC converter uses the latest and most advanced microcontroller International (MCU) And surface mount technology (SMT) Reliable performance, high accuracy, low power consumption, zero stability, convenient parameter setting. Click the Chinese display LCD , Display the cumulative flow, instantaneous flow velocity, flow percentage and so on. ZRN-LDC electromagnetic flowmeter measurements in closed conduits for conducting liquid and slurry volume flow, such as clean water, sewage, various chemical salt solution, slurry, pulp, pulp and liquid foods such respect.
• Bi-directional measurement system can measure forward flow, reverse flow. Using a special production process and quality materials to ensure product performance remains stable over the long term.
Electromagnetic Flowmeter Selection
Instrumentation instrument selection is very important work, the data indicate that the instrument in practical applications have 2/3 Selection of instrument failure is wrong or incorrect installation caused, please pay special attention.
Electromagnetic Flowmeter Selection Instructions correctly chosen electromagnetic flowmeter is a prerequisite to ensure the good use of electromagnetic flowmeters. Shiyao kind of electromagnetic flowmeter selection should be determined based on the physical and chemical properties of the measured fluid medium that bore electromagnetic flowmeter, flow range, lining materials, electrode materials and output current, etc., can meet the requirements of the measured fluid properties and the nature and flow of measurable fluid: From working principle of electromagnetic flowmeters, electromagnetic flowmeters can choose fluid flow measurement must be electrically conductive, strictly speaking, in addition to the high temperature fluid, any fluid as long as the conductivity is greater than 5μ / cm are chosen corresponding electromagnetic flowmeter to measure the flow rate, and therefore non-conductive material gas, steam, oil, acetone, etc. You can not use electromagnetic flowmeter to measure the flow rate determination sensor diameter: Flowmeter flow rate is preferably in the 0.3-15m / s range, this time in line with user selectable meter diameter pipe diameter using a flow rate of less than 0.3m / s. The best parts of the instrument when local increase in the flow rate, using shrink tube way: when the central cone angle diameter pipe is not more than 15oC, can be seen as the straight pipe diameter pipe portion of a body or a separate type of selection: Compact: live under better environmental conditions, generally use a body, namely the sensor and converter assembled into one.
| model | caliber | |||||
| ZRN-LDC | 15~2600 | |||||
| Code | Electrode material | |||||
| K1 | 316L | |||||
| K2 | HB | |||||
| K3 | HC | |||||
| K4 | titanium | |||||
| K5 | Tantalum | |||||
| K6 | Platinum alloy | |||||
| K7 | Stainless steel coated with tungsten carbide | |||||
| Code | Lining material | |||||
| C1 | Teflon F4 | |||||
| C2 | Poly FEP F46 | |||||
| C3 | Polyvinyl fluoride, ethylene co-FS | |||||
| C4 | Poly recorded butadiene rubber | |||||
| C5 | Polyurethane rubber | |||||
| Code | Features | |||||
| E1 | 0.3 | |||||
| E2 | 0.5 | |||||
| E3 | Level 1 | |||||
| F1 | 4-20Madc, load ≤750Ω | |||||
| F2 | 0-3khz, 5v active, variable pulse width output high effective frequency | |||||
| F3 | RS485 interface | |||||
| T1 | Std | |||||
| T2 | High temperature | |||||
| T3 | Ultra-high temperature type | |||||
| P1 | 1.0MPa | |||||
| P2 | 1.6MPa | |||||
| P3 | 4.0MPa | |||||
| P4 | 16MPa | |||||
| D1 | 220VAC ± 10% | |||||
| D2 | 24VDC ± 10% | |||||
| J1 | A body structure | |||||
| J2 | Sub-body structure | |||||
| J3 | Explosion-proof body structure | |||||
• Data collection
① measured fluid ingredients ② maximum flow, minimum flow ③ ④ maximum working pressure maximum temperature, minimum temperature
Installation Site Selection
In order to make stable and reliable electromagnetic flowmeter, when selecting the mounting location in attention to the following requirements:
1. Try to avoid ferromagnetic objects and devices with strong electromagnetic fields (large electric motors and transformers, etc.), so as not to affect the magnetic field and the magnetic flow sensor signal.
2. should be installed in dry and ventilated place, avoid the sun and rain, ambient temperature should be -20 ~ + 60 ℃, relative humidity less than 85%.
3. The meter should be ample space around, easy to install and maintain.
Electromagnetic flowmeter measurement principle does not depend on the flow characteristics, if there is a certain degree of turbulence inside the pipe and the vortex is generated in the non-measurement area (such as: elbows, tangential limiting or upstream half open valve) is the measurement If there is nothing to steady vortex it will affect the stability and measurement precision measurement, then you should take some measures to stabilize the velocity distribution in the measurement area:
. a increase in the length of straight pipe section before and after;
. b using a flow stabilizer;
c. to reduce the cross section of the measuring point.
Electrode materials selection:
| material | Anti-corrosion properties |
| 316L | Application: 1, domestic water, industrial water, raw water wells, municipal sewage. 2, weak corrosive acid, alkali, salt solution |
| Hastelloy B | Applicable: 1, hydrochloric acid (concentration less than 10%), ammonium hydroxide concentration of the alkaline solution all 2, sodium hydroxide (concentration less than 50%), ammonium hydroxide concentration in the alkali solution all 3, phosphoric acid, an organic acid NA: hydrochloric acid |
| Hastelloy C | Application: 1, mixed acid such as chromic acid and sulfuric acid mixed solution 2, an oxidizing salts such as Fe ++, Cu ++, seawater NA: hydrochloric acid |
| Titanium (Ti) | Applicable: 1, salts, such as: (1) chloride (chloride / magnesium / aluminum / calcium / ammonium / titanium, etc.) (2) the sodium, potassium, ammonium, hypochlorite, water 2, the hydrogen concentration is less than 50% of potassium chloride, ammonium hydroxide, barium hydroxide alkaline solution NA: hydrochloric acid, sulfuric acid, phosphoric acid, hydrofluoric acid, an alkali cyanide barium oxide solution |
| Tantalum (Ta) | Application: 1, hydrochloric acid (concentration of less than 40%), sulfuric acid and concentrated sulfuric acid (not including oleum) 2, chlorine dioxide, magnesium chloride, hypochlorous acid, sodium cyanide, lead acetate 3, nitric acid (including fuming nitric acid), and other oxidizing acid, the temperature is below 80 ℃ in aqua regia NA: alkali, hydrofluoric acid |
| Platinum (Pt) | Application: Almost all of the acid, alkali, salt solutions (including fuming sulfuric acid, fuming nitric acid) NA: aqua regia, ammonium salt |
Electromagnetic flowmeter liner material selection:
It should be based on the measured medium corrosive, abrasive and temperature to choose the lining material.
PTFE
Translation: Teflon FEP
FEP
Protection class selection:
1, IP65 : Anti-water type, from any direction to allow the tap water sensor, water pressure 30kPa, the amount of water
2, IP68: diving, long-term work in the water.
Protection rating should be selected according to the actual situation, the sensor mounted below ground, as is often affected by flooding should be used in IP68, the sensor is installed above ground should be used IP65.
Select additional functions
LDE Basic intelligent electromagnetic flowmeter has a display, output 4-20mA and 0-1kHz alarm function, selected additional functions can be added according to the actual situation.
3, split installation: The sensor must be installed below ground level or other reasons, you should choose split installation.
4, RD-485 Communication: the need converters and other communications equipment, you need to choose RS-485 communication function.