| Model | ||
| Item | ARC2232aK | AR2232aT |
| Scope of Application | Combustible gas such as alkanes and combustible vapor like volatile organic matters such as alcohol and gasoline | |
| Detection Principle | Catalytic combustion | |
| Sampling Mode | Diffusion | |
| Measurement Range | 0~100%LEL | |
| Alarm Error | ± 3%LEL | |
| Response Time | ≤ 30S | |
| Working Voltage | DC24± 6 V | |
| Power Consumption | 1.5W (DC24V) | 1W (DC24V) |
| Operating Environment | Temperature: -40C~+70C; Relative humidity: ≤ 93%RH; Pressure: 86~106kPa | |
| Connecting Thread of Outgoing Line Hole | ||
| G3/4 pipe thread (internal) | ||
| Signal Output | Alarm: Passive normally-on contact output of electric relay | |
| Trouble: Passive normally-off contact output of electric relay (contact capacity: DC24V/ 1A) | 4-20mA standard signal | |
| Ex-factory alarm set value: | ||
| 25%LEL (default) | Maximum load resistance: ( ( 250 (≥ 16VDC) , 500 (≥ 20VDC) | |
| Explosion-proof Grade | Exd IICT6 | |
| Protection Grade | Up to IP66IP66 | |
| Transmission Distance: | ≤ 1000m (RVV3* 1.0mm2 ) | |
| Sensor Service Life | Three years (average) | |
| Sensor Storage Temperature | -25? ~+55? | |