2000kw/2500kVA Power Plant Diesel Generator

2000kw/2500kVA Power Plant Diesel Generator

bargain

add to cart
Model NO. HGM2750
Installation Method Fixed
Cooling Method Water Cooling
Certificates CE&ISO9001SO9001O9001
Warranty 1 Year or 1000 Operation Hours
Engine Model Googol Qta4320-G7
Trademark HONNY
Specification ISO8528
HS Code 8502120000
Type Self-Starting Diesel Generator
Stroke Four Stroke
Output Type AC Three Phase
Types Silent/Trailer/Open/Container/Base Oil Tank
Dimension 6200X2600X2800mm
Weight 16800kg
Transport Package Poly Plastic Firm or as Need
Origin Donguan, Guangdong, China
2000kw/2500kVA power plant diesel generator
HGM2750: Standby 2200kw/2750kVA 50Hz, 1500rpm, 400V/230V adjustable
Performance Feature
Engine and alternator shall be mounted on a same frame steel skid.
Built-in damper for anti-vibration.
Small size, low weight, easy to operating, installation and maintenance.
World most famous brand diesel engine. US Googol
World famous brand AC alternator: Stamford, Marathon, Leroy Somer, MVC.
Advanced and reliable control module: Key start, Auto start, Remote control by PC with RS232/485
Full range protect function and alarm shutdown feature.
Alternator Feature
1)Brush-less, 4 poles, rotation magnet.
2)IP21-23(NEMA1) enclosure is standard for all industrial alternators.
3)The insulation system is Class H
4)Simple installation and maintenance, with easy access to terminals, rotating diodes
5)Wide range of flange adaptors and single bearing disc coupling.
6)Standard 2/3 pitch windings avoid excessive neutral currents
7)AVR auto voltage regulator, auto exciter, auto adjustment
Standard Control System: GCS6410 AMF
Mains 3 phases VPh-N L1-N L2-N L3-N
Mains 3 phases VPh-pH L1-L2 L2-L3 L3-L1
Mains frequency Hz (L1)
Gen 3 phases VPh-N L1-N L2-N L3-N
Gen 3 phases VPh-pH L1-L2 L2-L3 L3-L1
Gen 3 phases current I1 I2 I3
Gen frequency Hz (L1)
Gen total apparent power ∑ Aum; Aum; A
Gen total active power ∑ Pum; Pum; P
Gen power factor PF (AV)
Genset speed RPM (signal from generator voltage frequency)
Engine oil pressure Bar (signal from engine P-sensor)
Engine coolant temperature (signal from engine T-sensor)
Battery voltage VDC
Genset Running hour Hour
Standard Accessory
Common steel base frame, Damper, Exhaust silencer, Flexible pipe, Battery connecting wires, Operation manual and document.
Optional Accessory
Circuit breaker, Starting Battery, Engine coolant and oil heater, Alternator space heater, Cooling for heat exchanger, Control system with RS232/485 communication interface, Battery charger by main supply, Fuel-water separator, Daily fuel tank, ATS and paralleling system, Soundproof Canopy and Moving Trailer.
Let's achieve our goal together, Using power to kindle the dream of human.
Generator Set Genset Model HGM2750
Rating Power (KW/KVA) 2000/2500
Standby Power(KW/KVA) 2200/2750
rating Ammeter(A) 3608

Diesel Engine
Engine Model QTA4320-G7
Prime Power(KW) 2169
Standby Power(KW) 2379
Bore X Stroke (mm) 170X195
number of Cylinder & Configurationationation 16 V
Displacement(l) 70.8
Compression Ratio 13.5:1
Aspiration Turbocharged & Aftercooledooledooled
Max. intake depression(kPa) 6
Combustion air Volume(m³/min);/min);/min) 158
Max. Exhaust back Pressure(kPa) 10
Exhaust Gas Flow(m³/min);/min);/min) 412
Max. Exhaust Gas Temperature (ºC)rdm;C)rdm;C) 450
Cooling Water cooled with Radiator
Fan cooling air flow(m³/min);/min);/min) 2000
Engine Coolant capacity(l) 260
Max. temperature of coolant (ºC)rdm;C)rdm;C) 100
Max. permissible oil temp (ºC)rdm;C)rdm;C) 100
Total oil capacity(l) 240
Rating Fuel Consumption(l/h) 492
Governing Type Electrical

Alternator
Rating Voltage(V) 400/230 adjustable
Alternator Model EN500L-2000N ENGGA
Rating Capacity(KW/KVA) 2000/2500
Eff.% 96.0%
Power Factor 0.8 lagged
Exciting type Brushless, PMG exciter, AVR
Voltage regulation ±0.5%smn;0.5%smn;0.5%
No. of Phase 3 phase 4 wire
Enclosure Class IP21
Class of Insulation H
Battery Rating Capacity(AH) 4X200AH 12V
Dimension Generator set dimension (LXWXH) 6500X2300X3000 mm
Weight Generator set Net Weight (kg) 15500