A22-EK10C pushbutton contacts
Standards compliant:
IEC/EN60947 VDE 0660
Mechanical life:
Operating frequency: ﹥10 x 106
Operating frequency: ≤6000 times/H
Operating force: ≤5N
Protection class: IP20
Climate protection: heat, continue, in line with IEC 60068-2-78
Heat cycle, in line with IEC 60068-2-30
Ambient temperature:
Open wide: -25/+60°C
Airtight: -25/+40°C
Installation location: arbitrarily
Withstand mechanical shock, to IEC 60068-2-27
Impact of continued 11ms, half-sine: ﹥30g
Connection cross section:
Single Line: 0.75-2.5mm
2Multi-strand cord: 0.5-1.5 mm
2Contact:
Rated impulse withstand voltage: 6000V AC
Rated insulation voltage: 500V
Overvoltage category/pollution degree: Ⅲ/3
Control circuit reliability: at 24V DC/5 mA
Possibility of failure: <10-7, in 107 operations in less than failure at 5V DC/1mA
Possibility of failure: <5 x 10-6, in 5 x 106 times less than once a fault operation
Maximum short-circuit protection device: fuse less
Model: PKZM0-10/FAZ-B6
Configuration fuse: 10A
Switching capacity:
Rated operating current: AC-15/115V Ⅰ/6A/230V Ⅰ/6A/400V Ⅰ/4A/500V Ⅰ/2A/DC-13/24V Ⅰ/3A/60V Ⅰ/3A/110V Ⅰ/0.8A/220V Ⅰ/0.3A
Electrical life: AC-15/230V/0.5A
Operating frequency: 1.6 x 106/230V/1.0A
Number of operations: 1 x 106/230V/3.0A
Operating frequency: 0.7 x 106/DV-13/12V/2.8A
Operating frequency: 1.2 x 106
A22-EK10C A22-EK10C A22-EK10C +NZM2-4-250-XKCO +NZM2-4-250-XKCU NZM2-4-250-XKC NZM2-XKS NZM2-4-XKS NZM2-XKA NZM2-4-XKA +NZM2-XKRO +NZM2-XKRU NZM2-XKR +NZM2-4-XKRO +NZM2-4-XKRU NZM2-4-XKR +NZM2-XKR4O +NZM2-XKR4U NZM2-XKR4 NZM2-XSTS NZM2-XKSA NZM2-4-XKSA NZM2-XKSFA NZM2-4-XKSFA NZM2-XIPK NZM2-4-XIPK NZM2-XIPA NZM2-4-XIPA NZM2-XKS185 NZM2-XSVHI NZM2-XSVR NZM2-4-XFIA30 NZM2-4-XFIA NZM2-XCI43-TVD NZM2-XCI43-TVDVR NZM2-XCI45-TVD NZM2-XCI45-TVDVR NZM2-XRAV NZM2-XRAVR NZM2-XMVR NZM2/3-XMVR NZM2-XMVRL NZM2/3-XMVRL NZM3-XDVR NZM3-XTVDV NZM3-XTVDVR NZM3-XTVD-60 NZM3-XTVDV-60 NZM3-XTVDVR-60 NZM3-XTVD-0 NZM3-XTVDV-0 NZM3-XTVDVR-0 NZM3/4-XDZ NZM3-XBR NZM3-XAB NZM3-XHB NZM3-XHBR |